跳转到主要内容

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term MM OM3 96c OFNP xxxM Aqua pulling eye one side

Description

Description

Standards

ISO/IEC 11801

Pre-Term for data centres, buildings and campus based on Micro-Bundle.

The cable has a small diameter and bend raduis to meet data centre requirements.

Fire performance

The cables have been tested for fire performance according to Plenum rated, providing a very high fire performance with minimal fire load and can be used in air flow space.

MPO-MPO Pre-Term characteristics

The MPO-MPO Pre-Term has standard pinned (male) connectors. This matches with the un-pinned (female) connectors in the female Plug&Play modules.

The "xxx" in the N-number is the length in meter between the cable glands, i.e. the Pre-Term length between the back side of the patch panels.

After the cable gland the Pre-Term has a fan-out. The fan-out splits the cable into tubes. The tubes are reinforced with aramid yarns.

The pulling eye provides minimum 450N installation tension. Prefabricated pulling eye is available with this MPO pre-term. 

The MPO-MPO Pre-Terms come with a PG-13 cable gland that fits into the LANmark-OF Plug&Play patch panel slots.

Optical Performance and Polarity

The insertion loss for a multimode the MPO-MPO connection has  Low Loss performance: typical insertion loss is 0,2 dB with a maximum of 0,35 dB insertion loss. The insertion loss of a MPO-MPO connection is measured according to standard IEC61300-3-45.

The minimum return loss for a multimode MPO connection is 20 dB measured according to IEC 61300-3-6.

The method C Pre-Term has a pair flip key up / key down design. This is in agreement with standard TIA-568.3-D-2016 method C.

Characteristics

Characteristics

结构特性
光纤类型
OM3 50/125
尺寸特性
光纤数
96
标称外径
10.0 mm
机械特性
机械耐冲击性能
10次冲击/ 3N.M
耐挤压 (IEC 794-1-E3)
100 N/cm
最大安装拉力
1000 N
传输特性
最大插入损耗,dB
0.35 dB
最小回波损耗,dB
20 dB
使用特性
操作温度,范围
-20...60 °C
最小弯曲半径 - 动态
20 (xD)
最小弯曲半径 - 静态(XD)
10