LANmark-OF ENSPACE Method C MTP-MTP Pre-Term LSZH APAC

Products

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term SM 12c Low Loss LSZH xxxM OS2 G.657.A1 Yellow

Aginode ref. N144.C12MMExxxY

  • Fiber optic type: SM (G657.A1)
  • Number of optical fibres: 12

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term SM 24c Low Loss LSZH xxxM OS2 G.657.A1 Yellow

Aginode ref. N144.C24MMExxxY

  • Fiber optic type: SM (G657.A1)
  • Number of optical fibres: 24

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term SM 48c Low Loss LSZH xxxM OS2 G.657.A1 Yellow

Aginode ref. N144.C48MMExxxY

  • Fiber optic type: SM (G657.A1)
  • Number of optical fibres: 48

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term SM 96c Low Loss LSZH xxxM OS2 G.657.A1 Yellow

Aginode ref. N144.C96MMExxxY

  • Fiber optic type: SM (G657.A1)
  • Number of optical fibres: 96

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term MM 12c Low Loss LSZH xxxM OM3 Aqua

Aginode ref. N145.C12MMExxxA

  • Fiber optic type: OM3 50/125
  • Number of optical fibres: 12

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term MM 24c Low Loss LSZH xxxM OM3 Aqua

Aginode ref. N145.C24MMExxxA

  • Fiber optic type: OM3 50/125
  • Number of optical fibres: 24

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term MM 48c Low Loss LSZH xxxM OM3 Aqua

Aginode ref. N145.C48MMExxxA

  • Fiber optic type: OM3 50/125
  • Number of optical fibres: 48

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term MM 96c Low Loss LSZH xxxM OM3 Aqua

Aginode ref. N145.C96MMExxxA

  • Fiber optic type: OM3 50/125
  • Number of optical fibres: 96

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term MM 12c Low Loss LSZH xxxM OM4 Aqua

Aginode ref. N147.C12MMExxxA

  • Fiber optic type: OM4 50/125
  • Number of optical fibres: 12

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term MM 24c Low Loss LSZH xxxM OM4 Aqua

Aginode ref. N147.C24MMExxxA

  • Fiber optic type: OM4 50/125
  • Number of optical fibres: 24

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term MM 48c Low Loss LSZH xxxM OM4 Aqua

Aginode ref. N147.C48MMExxxA

  • Fiber optic type: OM4 50/125
  • Number of optical fibres: 48

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term MM 96c Low Loss LSZH xxxM OM4 Aqua

Aginode ref. N147.C96MMExxxA

  • Fiber optic type: OM4 50/125
  • Number of optical fibres: 96

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term MM 12c Low Loss LSZH xxxM OM5 Lime Green

Aginode ref. N149.C12MMExxxL

  • Fiber optic type: OM5 50/125 Wideband
  • Number of optical fibres: 12

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term MM 24c Low Loss LSZH xxxM OM5 Lime Green

Aginode ref. N149.C24MMExxxL

  • Fiber optic type: OM5 50/125 Wideband
  • Number of optical fibres: 24

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term MM 48c Low Loss LSZH xxxM OM5 Lime Green

Aginode ref. N149.C48MMExxxL

  • Fiber optic type: OM5 50/125 Wideband
  • Number of optical fibres: 48

 

LANmark-OF ENSPACE Method C MTP/M-MTP/M Pre-Term MM 96c Low Loss LSZH xxxM OM5 Lime Green

Aginode ref. N149.C96MMExxxL

  • Fiber optic type: OM5 50/125 Wideband
  • Number of optical fibres: 96

 

Description

Description

Standards

ANSI/TIA-568-C.3; ISO/IEC 11801

Pre-Term for data centres, buildings and campus based on Micro-Bundle Universal

The cable has a small diameter and bend raduis to meet data centre requirements.

Fire performance

The cables have been tested for fire performance according to IEC 60332-3c. The cable meets LSZH requirements.

MTP*-MTP Pre-Term characteristics

The MTP-MTP Pre-Term has standard pinned (male) connectors. This matches with the un-pinned (female) connectors in the ENSPACE modules and the female Plug&Play modules.

In order to reduce overlengths in data centers the Pre-Terms are custom made and available with 1m increments. The "xxx" in the N-number is the length in metre between the cable glands, i.e. the Pre-Term length between the back side of the patch panels.

The Pre-Terms are optimized for both pulling and laying in data centers. On both sides the MTP connectors are protected by a bubble foam. The maximum pulling force on the pulling eye is 450N. The detachable pulling eye with corrugrated tube can be ordered using PN N890.100HP.

The MTP-MTP Pre-Terms come with a PG-13 cable gland that fits into the LANmark-OF ENSPACE and Plug&Play patch panel slots.

Optical Performance and Polarity

The insertion loss for a multimode the MTP-MTP* connection has Low Loss performance: typical insertion loss is 0,15 dB with a maximum of 0,35 dB insertion loss. Ultra Low loss is also available with typical insertion loss 0.125dB with a maximum of 0.25dB insertion loss.

The insertion loss for a singlemode the MTP-MTP* connection has Low Loss performance:  typical insertion loss 0.3dB with a maximum of 0.35dB insertion loss.

The insertion loss of a MTP-MTP* connection is measured according to standard IEC61300-3-45.

The minimum return loss for a multimode MTP connection is 20 dB measured according to IEC 61300-3-6. The minimum return loss for a singlemode MTP connection is 45 dB measured according to IEC 61300-3-6.

The method C Pre-Term has a pairflip key up / key down design. This is in agreement with standard TIA-568.3-D-2016 method C.

Characteristics

Characteristics

Construction characteristics
Fiber optic type
OM3 50/125
Halogen free
Yes
Dimensional characteristics
Number of optical fibres
96
Nominal outer diameter
6.4 mm
Mechanical characteristics
Mechanical resistance to impacts
10 impacts of 3 N.m
Crush resistance (IEC 60794-1-E3)
100 N/cm
Maximum installation tension
1000 N
Transmission characteristics
Insertion Loss, maximum, dB
0.35 dB
Return Loss, Minimum, dB
20 dB
Usage characteristics
Operating temperature, range
-20...60 °C
Fire retardant
IEC 60332-3-24 (cat C)
Smoke density
IEC 61034
Minimum dynamic operating bending radius
20 (xD)
Minimum bending radius, static (XD)
10