Skip to main content

LANmark-OF Micro-Bundle Universal (6F-12F) Dca

Products

Description

Description

Standards

ISO/IEC 11801

Description and Application
 The new Micro-Bundle technology from Aginode allows to manufacture a very flexible and small tube that is the central part of the new “LANmark-OF Micro-Bundle Universal” cable design. This results in a small, flexible, but mechanical robust cable. The central tube contains up till 12 fibres with a fibre diameter of 250 um. Termination of these fibres is done with splicing with pigtails.

The small bending radius of the Micro-Bundle makes the cable easy to arrange in patch panels and for installations in data centres and backbones. 

The watertight glass yarns and the very limited amount of gel inside the tube makes this cable design watertight and suitable for installation outdoor in a duct by pulling.

The fire performance of the LANmark-OF Micro-Bundle Universal allows indoor installation as well. Since there is no drip effect of the very limited amount of gel the cable is optimised for both horizontal and vertical installations.

 

Construction

  1. Central Micro-Bundle
  2. Optical fibres (250 µm)
  3. Reinforced watertight glass yarns
  4. Ripcord
  5. LSZH outer jacket with UV resistant additive

 

Characteristics

  • Indoor cable for horizontal and vertical installation
  • Outdoor cable for installation in a duct
  • Designed for termination by splicing
  • Central Micro-Bundle design for easy installation
  • All dielectric
  • Waterproof structure, Rodent retardant and UV-resistant
  • Flame retardant (IEC 60332-1) and fire retardant (IEC 60332-3)
  • Available in all fibre grades and from 4-12 fibres
  • Gas Toxicity (IEC 60754) and Smoke Density (IEC61034)

     

Characteristics

Characteristics

Construction characteristics
Fiber optic type
SM (G657.A1)
Dimensional characteristics
Number of optical fibres
6
Mechanical characteristics
Mechanical resistance to impacts
1 impact of 3 N.m
Maximum operating pulling force
700 N
Maximum pulling force (IEC 60794-1-2-E1)
2200 N
Crush resistance (IEC 60794-1-E3)
200 N/cm
Usage characteristics
Operating temperature, range
-20...60 °C
Fire retardant
IEC 60332-3
Minimum dynamic operating bending radius
60.0 mm
Minimum static operating bending radius
60 mm
Flame retardant
IEC 60332-1
Storage temperature, range
-40...60 °C
Ambient installation temperature, range
0...40 °C

Contact us

Topics on which you wish to get more informations:

Required fields*

CAPTCHA
20 + 0 =
Solve this simple math problem and enter the result. E.g. for 1+3, enter 4.
This question is for testing whether or not you are a human visitor and to prevent automated spam submissions.

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes