Skip to main content

AGINODE D-CORE 2x16 BA+RG LSZH Eca 500M

Description

Description

Standards

IEC 60332-1; IEC 60502-1

Applications

  • Power cable 0.6/1.0 kV
  • For indoor/outdoor applications
  • Used on mobile phone masts



Cable construction

  1. Bare conductor strand - Class 5
  2. Insulation (IEC 60811-1)XLPE
  3. Longitudinal ALU/PET tape
  4. Tinned copper braid (Coverage US >65%)
  5. Outer sheath: Eca
    HFFR - Black


Environment
Designed to reduce the environment impact, Aginode cables are compliant with RoHS 2011/65 Directive and European Reach 1907/2006/EC regulation.

D-CORE Picture

Characteristics

Characteristics

Construction characteristics
Screen
Aluminium-Polyester tape + tinned copper braid
Outer sheath
LSZH
Sheath colour
Black
Wire colour
White - Red
Conductor material
Bare copper class 5
Insulation
XLPE
Dimensional characteristics
Approximate weight
430 kg/km
Outer Diameter
14.5 mm
Number of cores
2
Conductor cross-section
16 mm²
Diameter over insulation, range
5.9...6.1 mm
Electrical characteristics
Max. DC resistance of the conductor at 20°C
1.21 Ohm/km
Minimum insulation resistance
10 MOhm.km
Breakdown voltage Vcc, 5 min.
3500.0 V
Usage characteristics
Gases corrosivity
IEC 60754-1; IEC 60754-2
Operating temperature, range
-40...90 °C
Flame retardant
IEC 60332-1
Smoke density
EN/IEC 61034-2
Packaging
Drum 500 m
Storage temperature, range
-40...50 °C
Bending factor when laying
8 (xD)
Bending factor when installed
4 (xD)

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

CAPTCHA
3 + 4 =
Solve this simple math problem and enter the result. E.g. for 1+3, enter 4.
This question is for testing whether or not you are a human visitor and to prevent automated spam submissions.

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes