LANmark-OF ENSPACE Method B MTP-MTP Pre-Term OFNP APAC
LANmark-OF ENSPACE Method B MTP-MTP Pre-Term OFNP APAC
- Factory terminated MTP-MTP fibre assembly
- Flexible fan-out for ease of installation in patch panel
- Small cable diameter reduces required data centre space
- Method B polarity Pre-Term
- Optmized for 40G/100G parallel applications
- Fibre count: 12F, 24F, 48F, 96F and 144F
- Fibre type: OM3, OM4 and singlemode (OS2)
LANmark-OF ENSPACE Method B 12F x SM Ultra Low Loss MTP Male APC - MTP Male APC Pre-Term xxxm OFNP Yellow
Aginode ref. N144.O12MMExxxY
- Fiber optic type: SM (G657.A1)
- Nominal outer diameter: 4.5 (mm)
- Number of optical fibres: 12
- Crush resistance (IEC 60794-1-E3): 100 (N/cm)
- Maximum installation tension: 450 (N)
- Mechanical resistance to impacts: 10 impacts of 3 N.m
- Return Loss, Minimum, dB: 45 (dB)
- Insertion Loss, maximum, dB: 0.35 (dB)
- 操作温度范围: -20...60 (°C)
- Minimum bending radius, static (XD): 10
- Minimum dynamic operating bending radius: 20 ((xD))
LANmark-OF ENSPACE Method B 24F x SM Ultra Low Loss MTP Male APC - MTP Male APC Pre-Term xxxm OFNP Yellow
Aginode ref. N144.O24MMExxxY
- Fiber optic type: SM (G657.A1)
- Nominal outer diameter: 7.5 (mm)
- Number of optical fibres: 24
- Crush resistance (IEC 60794-1-E3): 100 (N/cm)
- Maximum installation tension: 660 (N)
- Mechanical resistance to impacts: 10 impacts of 3 N.m
- Return Loss, Minimum, dB: 45 (dB)
- Insertion Loss, maximum, dB: 0.35 (dB)
- 操作温度范围: -20...60 (°C)
- Minimum bending radius, static (XD): 10
- Minimum dynamic operating bending radius: 20 ((xD))
LANmark-OF ENSPACE Method B 48F x SM Ultra Low Loss MTP Male APC - MTP Male APC Pre-Term xxxm OFNP Yellow
Aginode ref. N144.O48MMExxxY
- Fiber optic type: SM (G657.A1)
- Nominal outer diameter: 7.7 (mm)
- Number of optical fibres: 48
- Crush resistance (IEC 60794-1-E3): 100 (N/cm)
- Maximum installation tension: 660 (N)
- Mechanical resistance to impacts: 10 impacts of 3 N.m
- Return Loss, Minimum, dB: 45 (dB)
- Insertion Loss, maximum, dB: 0.35 (dB)
- 操作温度范围: -20...60 (°C)
- Minimum bending radius, static (XD): 10
- Minimum dynamic operating bending radius: 20 ((xD))
LANmark-OF ENSPACE Method B 96F x SM Ultra Low Loss MTP Male APC - MTP Male APC Pre-Term xxxm OFNP Yellow
Aginode ref. N144.O96MMExxxY
- Fiber optic type: SM (G657.A1)
- Nominal outer diameter: 10.0 (mm)
- Number of optical fibres: 96
- Crush resistance (IEC 60794-1-E3): 100 (N/cm)
- Maximum installation tension: 1000 (N)
- Mechanical resistance to impacts: 10 impacts of 3 N.m
- Return Loss, Minimum, dB: 45 (dB)
- Insertion Loss, maximum, dB: 0.35 (dB)
- 操作温度范围: -20...60 (°C)
- Minimum bending radius, static (XD): 10
- Minimum dynamic operating bending radius: 20 ((xD))
LANmark-OF ENSPACE Method B 12F x OM3 MTP Male - MTP Male Pre-Term xxxm OFNP Aqua
Aginode ref. N145.O12MMExxxA
- Fiber optic type: OM3 50/125
- Nominal outer diameter: 4.5 (mm)
- Number of optical fibres: 12
- Crush resistance (IEC 60794-1-E3): 100 (N/cm)
- Maximum installation tension: 450 (N)
- Mechanical resistance to impacts: 10 impacts of 3 N.m
- Return Loss, Minimum, dB: 20 (dB)
- Insertion Loss, maximum, dB: 0.35 (dB)
- 操作温度范围: -20...60 (°C)
- Minimum bending radius, static (XD): 10
- Minimum dynamic operating bending radius: 20 ((xD))
LANmark-OF ENSPACE Method B 24F x OM3 MTP Male - MTP Male Pre-Term xxxm OFNP Aqua
Aginode ref. N145.O24MMExxxA
- Fiber optic type: OM3 50/125
- Nominal outer diameter: 7.5 (mm)
- Number of optical fibres: 24
- Crush resistance (IEC 60794-1-E3): 100 (N/cm)
- Maximum installation tension: 660 (N)
- Mechanical resistance to impacts: 10 impacts of 3 N.m
- Return Loss, Minimum, dB: 20 (dB)
- Insertion Loss, maximum, dB: 0.35 (dB)
- 操作温度范围: -20...60 (°C)
- Minimum bending radius, static (XD): 10
- Minimum dynamic operating bending radius: 20 ((xD))
LANmark-OF ENSPACE Method B 48F x OM3 MTP Male - MTP Male Pre-Term xxxm OFNP Aqua
Aginode ref. N145.O48MMExxxA
- Fiber optic type: OM3 50/125
- Nominal outer diameter: 7.7 (mm)
- Number of optical fibres: 48
- Crush resistance (IEC 60794-1-E3): 100 (N/cm)
- Maximum installation tension: 660 (N)
- Mechanical resistance to impacts: 10 impacts of 3 N.m
- Return Loss, Minimum, dB: 20 (dB)
- Insertion Loss, maximum, dB: 0.35 (dB)
- 操作温度范围: -20...60 (°C)
- Minimum bending radius, static (XD): 10
- Minimum dynamic operating bending radius: 20 ((xD))
LANmark-OF ENSPACE Method B 96F x OM3 MTP Male - MTP Male Pre-Term xxxm OFNP Aqua
Aginode ref. N145.O96MMExxxA
- Fiber optic type: OM3 50/125
- Nominal outer diameter: 10.0 (mm)
- Number of optical fibres: 96
- Crush resistance (IEC 60794-1-E3): 100 (N/cm)
- Maximum installation tension: 1000 (N)
- Mechanical resistance to impacts: 10 impacts of 3 N.m
- Return Loss, Minimum, dB: 20 (dB)
- Insertion Loss, maximum, dB: 0.25 (dB)
- 操作温度范围: -20...60 (°C)
- Minimum bending radius, static (XD): 10
- Minimum dynamic operating bending radius: 20 ((xD))
LANmark-OF ENSPACE Method B 12F x OM4 MTP Male - MTP Male Pre-Term xxxm OFNP Aqua
Aginode ref. N147.O12MMExxxA
- Fiber optic type: OM4 50/125
- Nominal outer diameter: 4.5 (mm)
- Number of optical fibres: 12
- Crush resistance (IEC 60794-1-E3): 100 (N/cm)
- Maximum installation tension: 450 (N)
- Mechanical resistance to impacts: 10 impacts of 3 N.m
- Return Loss, Minimum, dB: 20 (dB)
- Insertion Loss, maximum, dB: 0.35 (dB)
- 操作温度范围: -20...60 (°C)
- Minimum bending radius, static (XD): 10
- Minimum dynamic operating bending radius: 20 ((xD))
LANmark-OF ENSPACE Method B 24F x OM4 MTP Male - MTP Male Pre-Term xxxm OFNP Aqua
Aginode ref. N147.O24MMExxxA
- Fiber optic type: OM4 50/125
- Nominal outer diameter: 7.5 (mm)
- Number of optical fibres: 24
- Crush resistance (IEC 60794-1-E3): 100 (N/cm)
- Maximum installation tension: 660 (N)
- Mechanical resistance to impacts: 10 impacts of 3 N.m
- Return Loss, Minimum, dB: 20 (dB)
- Insertion Loss, maximum, dB: 0.35 (dB)
- 操作温度范围: -20...60 (°C)
- Minimum bending radius, static (XD): 10
- Minimum dynamic operating bending radius: 20 ((xD))
LANmark-OF ENSPACE Method B 48F x OM4 MTP Male - MTP Male Pre-Term xxxm OFNP Aqua
Aginode ref. N147.O48MMExxxA
- Fiber optic type: OM4 50/125
- Nominal outer diameter: 7.7 (mm)
- Number of optical fibres: 48
- Crush resistance (IEC 60794-1-E3): 100 (N/cm)
- Maximum installation tension: 660 (N)
- Mechanical resistance to impacts: 10 impacts of 3 N.m
- Return Loss, Minimum, dB: 20 (dB)
- Insertion Loss, maximum, dB: 0.35 (dB)
- 操作温度范围: -20...60 (°C)
- Minimum bending radius, static (XD): 10
- Minimum dynamic operating bending radius: 20 ((xD))
LANmark-OF ENSPACE Method B 96F x OM4 MTP Male - MTP Male Pre-Term xxxm OFNP Aqua
Aginode ref. N147.O96MMExxxA
- Fiber optic type: OM4 50/125
- Nominal outer diameter: 10.0 (mm)
- Number of optical fibres: 96
- Crush resistance (IEC 60794-1-E3): 100 (N/cm)
- Maximum installation tension: 1000 (N)
- Mechanical resistance to impacts: 10 impacts of 3 N.m
- Return Loss, Minimum, dB: 20 (dB)
- Insertion Loss, maximum, dB: 0.35 (dB)
- 操作温度范围: -20...60 (°C)
- Minimum bending radius, static (XD): 10
- Minimum dynamic operating bending radius: 20 ((xD))
설명
설명
Standards
Fire performance
The cables have been tested for fire performance according to UL Plenum performance.
According to this standard the cables have a very high fire performance with minimal fire load and can be used in air flow space.
MTP*-MTP Pre-Term characteristics
The MTP-MTP Pre-Term has standard pinned (male) connectors. This matches with the un-pinned (female) connectors in the ENSPACE modules and the female Plug&Play modules.
After the cable gland the Pre-Term has a fan-out. The fan-out splits the cable into tubes. The tubes are reinforced with aramid yarns. At the end of each tube a MTP-connectors is mounted. The jacket of the tube is the same colour as the cable jacket. Close to the MTP-connector a label is installed to identify the number of the leg.
The Pre-Terms are optimized for both pulling and laying in data centers. On both sides the MTP connectors are protected by a bubble foam. The maximum pulling force on the pulling eye is 450N. The detachable pulling eye with corrugrated tube can be ordered using PN N890.100HP.
The MTP-MTP Pre-Terms come with a PG-13 cable gland that fits into the LANmark-OF ENSPACE and Plug&Play patch panel slots.
Optical Performance and Polarity
The insertion loss for a multimode the MTP-MTP* connection has Low Loss performance: typical insertion loss is 0,25 dB with a maximum of 0,35 dB insertion loss.
The insertion loss for a singlemode the MTP-MTP* connection has Ultra Low Loss performance: typical insertion loss 0.25dB with a maximum of 0.35dB insertion loss.
The insertion loss of a MTP-MTP* connection is measured according to standard IEC61300-3-45.
The minimum return loss for a multimode MTP connection is 20 dB measured according to IEC 61300-3-6. The minimum return loss for a singlemode MTP connection is 45 dB measured according to IEC 61300-3-6.
The method B Pre-Term has a key up / key up design. This is in agreement with standard TIA-568.3-D-2016 method B.