LANmark-OF MPO-MPO Pre-Term OFNP Method C APAC

Produkte

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term MM OM3 12c OFNP xxxM Aqua

Nexans ref. N145.CU12LPxxx-PA

  • Fasertyp: OM3 50/125
  • Anzahl der optischen Fasern: 12
  • Insertion Loss, maximum, dB: 0,35 dB
  • Rückflussdämpfung, max. dB: 20 dB
  • Maximale Zugspannung bei Installation: 450 N

 

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term MM OM3 24c OFNP xxxM Aqua

Nexans ref. N145.CU24LPxxx-PA

  • Fasertyp: OM3 50/125
  • Anzahl der optischen Fasern: 24
  • Insertion Loss, maximum, dB: 0,35 dB
  • Rückflussdämpfung, max. dB: 20 dB
  • Maximale Zugspannung bei Installation: 660 N

 

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term MM OM3 48c OFNP xxxM Aqua

Nexans ref. N145.CU48LPxxx-PA

  • Fasertyp: OM3 50/125
  • Anzahl der optischen Fasern: 48
  • Insertion Loss, maximum, dB: 0,35 dB
  • Rückflussdämpfung, max. dB: 20 dB
  • Maximale Zugspannung bei Installation: 660 N

 

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term MM OM3 96c OFNP xxxM Aqua pulling eye one side

Nexans ref. N145.CU96LAxxx-PA

  • Fasertyp: OM3 50/125
  • Anzahl der optischen Fasern: 96
  • Insertion Loss, maximum, dB: 0,35 dB
  • Rückflussdämpfung, max. dB: 20 dB
  • Maximale Zugspannung bei Installation: 1000 N

 

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term MM OM4 12c OFNP Ultra Low loss xxxM Aqua

Nexans ref. N147.CU12UPxxx-PA

  • Fasertyp: OM4 50/125
  • Anzahl der optischen Fasern: 12
  • Insertion Loss, maximum, dB: 0,25 dB
  • Rückflussdämpfung, max. dB: 20 dB
  • Maximale Zugspannung bei Installation: 450 N

 

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term MM OM4 12c OFNP xxxM Aqua

Nexans ref. N147.CU12LPxxx-PA

  • Fasertyp: OM4 50/125
  • Anzahl der optischen Fasern: 12
  • Insertion Loss, maximum, dB: 0,35 dB
  • Rückflussdämpfung, max. dB: 20 dB
  • Maximale Zugspannung bei Installation: 450 N

 

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term MM OM4 24c OFNP xxxM Aqua

Nexans ref. N147.CU24LPxxx-PA

  • Fasertyp: OM4 50/125
  • Anzahl der optischen Fasern: 24
  • Insertion Loss, maximum, dB: 0,35 dB
  • Rückflussdämpfung, max. dB: 20 dB
  • Maximale Zugspannung bei Installation: 660 N

 

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term MM OM4 24c Ultra Low loss OFNP xxxM Aqua

Nexans ref. N147.CU24UPxxx-PA

  • Fasertyp: OM4 50/125
  • Anzahl der optischen Fasern: 24
  • Insertion Loss, maximum, dB: 0,25 dB
  • Rückflussdämpfung, max. dB: 20 dB
  • Maximale Zugspannung bei Installation: 660 N

 

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term MM OM4 48c OFNP xxxM Aqua

Nexans ref. N147.CU48LPxxx-PA

  • Fasertyp: OM4 50/125
  • Anzahl der optischen Fasern: 48
  • Insertion Loss, maximum, dB: 0,35 dB
  • Rückflussdämpfung, max. dB: 20 dB
  • Maximale Zugspannung bei Installation: 660 N

 

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term MM OM4 96c OFNP xxxM Aqua pulling eye one side

Nexans ref. N147.CU96LAxxx-PA

  • Fasertyp: OM4 50/125
  • Anzahl der optischen Fasern: 96
  • Insertion Loss, maximum, dB: 0,35 dB
  • Rückflussdämpfung, max. dB: 20 dB
  • Maximale Zugspannung bei Installation: 1000 N

 

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term SM OS2 G.657.A1 12c OFNP xxxM Yellow

Nexans ref. N144.CU12SPxxx-PY

  • Fasertyp: SM (G657.A1)
  • Anzahl der optischen Fasern: 12
  • Insertion Loss, maximum, dB: 0,75 dB
  • Rückflussdämpfung, max. dB: 45 dB
  • Maximale Zugspannung bei Installation: 450 N

 

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term SM OS2 G.657.A1 24c OFNP xxxM Yellow

Nexans ref. N144.CU24SPxxx-PY

  • Fasertyp: SM (G657.A1)
  • Anzahl der optischen Fasern: 24
  • Insertion Loss, maximum, dB: 0,75 dB
  • Rückflussdämpfung, max. dB: 45 dB
  • Maximale Zugspannung bei Installation: 660 N

 

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term SM OS2 G.657.A1 48c OFNP xxxM Yellow

Nexans ref. N144.CU48SPxxx-PY

  • Fasertyp: SM (G657.A1)
  • Anzahl der optischen Fasern: 48
  • Insertion Loss, maximum, dB: 0,75 dB
  • Rückflussdämpfung, max. dB: 45 dB
  • Maximale Zugspannung bei Installation: 660 N

 

LANmark-OF METHOD C MPO/M-MPO/M Pre-Term SM OS2 G.657.A1 96c OFNP xxxM Yellow pulling eye one side

Nexans ref. N144.CU96SAxxx-PY

  • Fasertyp: SM (G657.A1)
  • Anzahl der optischen Fasern: 96
  • Insertion Loss, maximum, dB: 0,75 dB
  • Rückflussdämpfung, max. dB: 45 dB
  • Maximale Zugspannung bei Installation: 1000 N

 

Beschreibung

Beschreibung

Normen

  • International
    ISO/IEC 11801

Pre-Term for data centres, buildings and campus based on Micro-Bundle.

The cable has a small diameter and bend raduis to meet data centre requirements.

Fire performance

The cables have been tested for fire performance according to Plenum fire performance, providing a very high fire performance with minimal fire load and can be used in air flow space.

MPO-MPO Pre-Term characteristics

The MPO-MPO Pre-Term has standard pinned (male) connectors. This matches with the un-pinned (female) connectors in the female Plug&Play modules.

In order to reduce overlengths in data centers the Pre-Terms are custom made and available with 1m increments. The "xxx" in the N-number is the length in metre between the cable glands, i.e. the Pre-Term length between the back side of the patch panels.

After the cable gland the Pre-Term has a fan-out. The fan-out splits the cable into tubes. The tubes are reinforced with aramid yarns. At the end of each tube a MPO-connectors is mounted. The jacket of the tube is the same colour as the cable jacket. Close to the MPO-connector a label is installed to identify the number of the leg.

Pre-terminated MPO fibre cable can be ordered separately with a removable pulling eye for fast deployment onsite. The pulling eye provides minimum 450N installation tension. High crush resistant pulling eye is also available with a high strength protection tube. The removable pulling eye can be quickly detached after installation and can be reinstalled, reducing construction waste and making it more suitable for sustainable environmental protection. Prefabricated pulling eye is also available with the MPO pre-term. The detachable pulling eye with corrugrated tube can be ordered using PN N890.100HP.

The MPO-MPO Pre-Terms come with a PG-13 cable gland that fits into the LANmark-OF Plug&Play patch panel slots.

Optical Performance and Polarity

The insertion loss for a multimode the MPO-MPO connection has Ultra Low Loss performance: typical insertion loss is 0,2 dB with a maximum of 0,35 dB insertion loss.

The typical insertion loss for a singlemode the MPO-MPO connection  is 0,5 dB with a maximum of 0,75 dB insertion loss.

The insertion loss of a MPO-MPO connection is measured according to standard IEC61300-3-45.

The minimum return loss for a multimode MPO connection is 20 dB . The minimum return loss for a singlemode MPO connection is 45 dB. The measurement is according to IEC 61300-3-6.

The MPO adopts method C, which has a pair flip key up / key down design. This is in agreement with standard TIA-568.3-D-2016 method C.

Eigenschaften

Eigenschaften

Mechanische Eigenschaften

Mechanische Eigenschaften

Mechanische Festigkeit gegen Schläge
10 impacts of 3 N.m
Querdruckwiderstand (IEC 794-1-E3)
100 N/cm

Anwendungsmerkmale

Anwendungsmerkmale

Betriebstemperatur
-20 ... 60 °C
Biegeradius min. nach Verlegung (xD)
10
Minimaler Biegeradius bewegt
20 (xD)

Ressourcen

Ressourcen

Kontaktieren Sie uns

Themen zu denen Sie weitere Informationen wünschen:

benötigte Felder*

Bitte überprüfen Sie Ihre Eingabe und versuchen Sie es erneut.

Eine Email Adresse muss ein einzelnes @ enthalten

Schutz personenbezogener Daten

Sie haben das Recht, der Verarbeitung Ihrer personenbezogenen Daten und / oder deren Verwendung für Direktmarketing- oder kommerzielle Zwecke zu widersprechen

Vielen Dank!

Danke, dass sie uns kontaktiert haben. Wir werden uns in Kürze mit Ihnen in Verbindung setzen.

Fehler

Ein Fehler ist aufgetreten. Bitte versuchen Sie es erneut.

Schliessen