LANmark-OF ENSPACE Patch Cord Duplex LC-ULL

Produkte

LANmark-OF ENSPACE Patch Cord DLC-DLC OM3 LSZH xm Aqua

Nexans ref. N122.5UUA x

  • Fasertyp: OM3 50/125
  • Insertion Loss, maximum, dB: 0,15 dB

 

LANmark-OF ENSPACE Patch Cord DLC-DLC OM4 LSZH xm Aqua

Nexans ref. N122.7UUA x

  • Fasertyp: OM4 50/125
  • Insertion Loss, maximum, dB: 0,15 dB

 

LANmark-OF ENSPACE Patch Cord DLC-DLC SM LSZH xm Yellow

Nexans ref. N122.4UUY x

  • Fasertyp: SingleMode 9/125
  • Insertion Loss, maximum, dB: 0,25 dB

 

Beschreibung

Beschreibung

Normen

  • International
    ISO/IEC 11801

Optimised for data centres environments

LANmark-OF ENSPACE patch cords have a very small bend radius of 10 mm due to the use GIGAliteFLEX bend insensitive fibre.

The small bend radius of the patch cord is beneficial in high density patching areas where a lot of bends are common. There is a high risk that the larger bend radius (40 mm) of traditional patch cords is not maintained resulting in high attenuation and loss of transmission.

The round design of the ENSPACE patch cord results in a small bend radius in any direction. Traditional patch cords based on a zipcord design have a bend radius that is dependent on the orientation.

With the round design and the small diameter (2mm) of the patch cable the area required for the patch cord is reduced by 50 % resulting in space savings, reduced disturbance of the airflow for cooling and easier patch cords management in high density racks.

For the support of the advanced high speed Ethernet protocols with stringent power budgets the ENSPACE patch cord features an Ultra low loss performance of 0.15 dB for OM3/OM4 and 0.25dB for OS2. This increases the headroom in the channel and reduces the risk of down time.

Characteristics

  • Patch cord cable is according to IEC 60794-2-50
  • Maximum insertion loss according to IEC 61300-3-4: 0.15 dB
  • Typical insertion loss: 0.1 dB
  • GIGAliteFLEX bend insensitive fibre
  • A label is added close to the uniboot connector for traceability of the measurement results

 

Guarantees and installation

Aginode LANmark-OF optical fibre patch cords have been designed for indoor applications in support of high speed protocols. Details on the supported distances can be found in the LANmark-OF warranty modules.

 

Typical installation environments are:

  • Cabinets to connect patch panels to active equipment.
  • Cross connects in data centres.

 

Design

Aginode LANmark-OF patch cords are delivered according to the "Cross-Over" wiring principle to improve field installation (A1-B2, B1-A2). This complies to the requirements of IEC 11801 and EN 50174-1:2009.

 

The polarity of the ENSPACE patch cord can be changed by opening the uniboot connector on one side and change the position of the 2 LC connectors. A black and yellow plastic square identify the fibre inside the patch cord.  The patch cords are delivered with the black square on the left on side A and on the right on side B.  This is required for cross-over or optical crossed patch cords. By changing the position of the black square on side A from the left to the right the patch cord becomes an optical straight patch cord. This straight patch cord can be used for some rare legacy applications that have a non-standard polarity.

Eigenschaften

Eigenschaften

Mechanische Eigenschaften

Mechanische Eigenschaften

Max. Zugkraft (IEC 60794-1-2-E1)
100 N
Mechanical resistance to impacts (IEC 60794-1-E4)
10 impacts of 1 N.m
Querdruckwiderstand (IEC 794-1-E3)
100 N/cm

Ressourcen

Ressourcen

Kontaktieren Sie uns

Themen zu denen Sie weitere Informationen wünschen:

benötigte Felder*

Bitte überprüfen Sie Ihre Eingabe und versuchen Sie es erneut.

Eine Email Adresse muss ein einzelnes @ enthalten

Schutz personenbezogener Daten

Sie haben das Recht, der Verarbeitung Ihrer personenbezogenen Daten und / oder deren Verwendung für Direktmarketing- oder kommerzielle Zwecke zu widersprechen

Vielen Dank!

Danke, dass sie uns kontaktiert haben. Wir werden uns in Kürze mit Ihnen in Verbindung setzen.

Fehler

Ein Fehler ist aufgetreten. Bitte versuchen Sie es erneut.

Schliessen