LANmark-OF METHOD C MPO/M-MPO/M Pre-Term MM OM4 12c Low Loss LSZH xxxM Aqua Pulling Eye one side

Description

Description

Normes

  • Normes internationales
    ISO/IEC 11801
  • Normes nationales
    ANSI/TIA-568-C.3

Pre-Term for data centres, buildings and campus based on Micro-Bundle Universal

The cable has a small diameter and bend raduis to meet data centre requirements.

Fire performance

The cables have been tested for fire performance according to IEC 60332-3c. The cable meets LSZH requirements.

MPO-MPO Pre-Term characteristics

The Pre-Term has standard pinned (male) MPO connectors. This matches with the un-pinned (female) connectors in the female Plug&Play MPO-LC modules.

In order to reduce overlengths in data centers the Pre-Terms are custom made and available with 1m increments. The "xxx" in the N-number is the length in metre between the cable glands, i.e. the Pre-Term length between the back side of the patch panels.

The Pre-Terms are optimized for both pulling and laying in data centers. On both sides the MPO connectors are protected by a bubble foam. The maximum pulling force on the pulling eye is 450N.

The MPO Pre-Terms come with a PG-13 cable gland that fits into the LANmark-OF Plug&Play patch panel gland holders.

Optical Performance and Polarity

The insertion loss for a singlemode the MPO connection has typical performance of 0.5dB with a maximum of 0.75dB insertion loss. The insertion loss of a MPO connection is measured according to standard IEC61300-3-45.

The minimum return loss for singlemode MPO connection is 45 dB, both measured according to IEC 61300-3-6.

The method B Pre-Term has a pair flip key up / key down design. This is in agreement with standard TIA-568.3-D-2016 method C.

Caractéristiques

Caractéristiques

Caractéristiques de construction

Caractéristiques de construction

Type de fibres optiques
OM4 50/125
Sans halogène
Oui

Caractéristiques dimensionnelles

Caractéristiques dimensionnelles

Nombre de fibres optiques
12
Diamètre externe nominal (mm)
3,65 mm

Caractéristiques de transmission

Caractéristiques de transmission

Insertion Loss, maximum, dB
0,35 dB
Return Loss, Minimum, dB
20 dB

Caractéristiques mécaniques

Caractéristiques mécaniques

Résistance mécanique aux chocs
10 impacts of 3 N.m
Résistance à l'écrasement (IEC 794-1-E3)
100 N/cm
Tension maximale à l’installation
450 N

Caractéristiques d'utilisation

Caractéristiques d'utilisation

Température ambiante d'utilisation, plage
-20 ... 60 °C
Minimum bending radius, static (XD)
10
Rayon de courbure minimum en utilisation dynamique
20 (xD)
Densité de fumée dégagée
IEC 61034
Non propagateur de l incendie
IEC 60332-3-24 (cat C)

Ressources

Ressources

Contactez-nous

Sujets sur lesquels vous souhaitez obtenir plus d'informations :

* Champs obligatoires

Veuillez vérifier votre saisie et réessayer.

Une adresse mail ne peut contenir qu'un seul @

Protection des données personnelles

Vous avez le droit de vous opposer au traitement de vos données personnelles et/ou à leur utilisation à des fins de marketing direct ou à des fins commerciales.

Merci !

Merci de nous avoir contactés. Nous vous contacterons sous peu.

Erreur

Une erreur s'est produite. Veuillez réessayer.

Fermer